114
GMD/W20 Series Carbon Dioxide Transmitters
for Demand Controlled Ventilation Applications
The duct mounted Vaisala
CARBOCAP
®
Carbon Dioxide
Transmitter Series GMD20 and
wall mounted GMW20 are specially
designed for Demand Controlled
Ventilation (DCV). They are easy to
install and require no maintenance.
The recommended calibration
interval is  ve years.
Vaisala CARBOCAP®
Technology
The GMD/W20 Series Transmitters
use the silicon-based Vaisala
CARBOCAP
®
Sensor. The simple
structure and reference measurement
capabilities make this Single-Beam,
Dual-Wavelength NDIR sensor
extremely stable and reliable.
The temperature and  ow
dependences of the sensor
are negligible. In addition, the
measurement accuracy is not
The GMD/W20 series transmitters are designed for use in ventilation-related
applications.
affected by dust, water vapor and
most chemicals.
Versatile Transmitters
The GMD/W20 series transmitters
can be used independently, or
incorporated into building energy
management systems. The series
consists of duct mount units
GMD20/D and wall mount units
GMW21/D and GMW22/D. Version D
has a display. The two sizes in the
wall-mount series make them easy
to install for most standard junction
boxes.
The duct units' compact sensor head
design requires only a small hole in a
ventilation duct, thereby minimizing
the risk of leaking gaskets and
measurement errors.
In addition to the standard
0 ... 20 mA, 4 ... 20 mA and 0 ... 10 V
outputs, there are three other
options: two LonWorks
®
interfaces
and a relay output. The relay output
is standard with the display units.
Improve Indoor Air at
Minimal Energy Costs
The use of the GMD/W20 series
transmitters ensures the best
possible control of air quality and
results in considerable savings in
energy consumption, maintenance
and recalibration costs.
Temperature Option
The GMA20T temperature module,
an option with the GMW21 wall
mount unit, combines both CO
2
and
temperature measurement into one
transmitter. The GMA20T has an
output of 0 ... 10 V corresponding to a
temperature range of 0 ... +50 °C
(+32 ... +122 °F).
Features/Benefi ts
Versatile transmitters
Duct and wall mount models
Incorporates Vaisala
CARBOCAP® Sensor - the
silicon-based NDIR sensor
Excellent long-term stability
Negligible temperature
dependence
Ease of installation
4-Carbon-Dioxide-Pages-100-119-Vaisala-Catalog-2011.indd 114 24.10.2011 9.22
115
Technical Data
Performance
CARBON DIOXIDE MEASUREMENT
Measurement range 0 ... 2000 ppm
(nominal; can be calibrated for other ranges:
0 ... 5000 ppm, 0 ... 10,000 ppm, 0 ... 20,000 ppm)
Accuracy (including repeatability, non-linearity
and calibration uncertainty) ± (2 % of range + 2% of reading)
Long-term stability <±5 % of range / 5 years
Response time (63%) 1 minute
Warm-up time 1 minute, 15 minutes full specifi cations
TEMPERATURE MEASUREMENT (OPTIONAL WITH GMW21)
Output signal 0 ... 10V
Corresponding measurement range 0 ... +50 °C (+32 ... +122 °F)
Accuracy at +25 °C ±0.5 °C (0.9 °F)
Warm up time 30 min
Temperature sensor Semiconductor IC
Accessories and Options
Display and relay option for GMD/W21/22 GMI21
Relay output option GMR20
LonWorks
®
module with CO
2
signal GML20
(Not available when display option is added)
LonWorks
®
module with both CO
2
signal
and temperature signals GML20T
(Not available when display option is added)
Serial COM adapter 19040GM
Analog temperature module for GMW21
(not available when display option is added) GMA20T
Hand-held meter for fi eld verifi cation GM70
Operating Environment
Temperature -5 ... +45 °C (+23 ... +113 °F)
Humidity 0 ... 85 %RH, non-condensing
Flow velocity (GMD20) 0 ... 10 m/s
Electromagnetic compatibility EN61326-1, Generic Environment
Mechanics
Housing material ABS plastic
Housing classifi cation (GMD20 electronics housing) IP65
Housing colour GMW21/22 NCS 0502-G50Y
Weight:
GMD20 (D) 140 g (170 g)
GMW21 (D) 100 g (130 g)
GMW22 (D) 90 g (120 g)
Inputs and Outputs
Outputs 0 ... 20 or 4 ... 20 mA and 0 ... 10 V
Optional outputs relay
LonWorks
®
interface
Resolution of analog outputs 8 bits
Recommended external load:
current output max. 500 ohm
voltage output min. 1 kohm
Operating voltage nominal 24 VAC/DC (18 ... 30 VDC)
Connections screw terminals, wire size 0.5 ... 1.5 mm
2
Power consumption <2.5 W
Ref. B210910EN-A ©Vaisala 2009
This material is subject to copyright protection, with all
copyrights retained by Vaisala and its individual partners. All
rights reserved. Any logos and/or product names are trademarks
of Vaisala or its individual partners. The reproduction, transfer,
distribution or storage of information contained in this brochure
in any form without the prior written consent of Vaisala is strictly
prohibited. All specifi cations — technical included — are subject
to change without notice.
For more information, visit
www.vaisala.com or contact
us at sales@vaisala.com
Dimensions
Dimensions in mm
GMD20 and GMD20D
GMW21 and GMW21D
GMW22 and GMW22D
CARBOCAP
®
is a registered trademark of Vaisala.
42
22
42
80
108.5
60
83
66.7
60
4-Carbon-Dioxide-Pages-100-119-Vaisala-Catalog-2011.indd 115 24.10.2011 9.22