HMP140A SERIES
U175en-1.5 Operating Manual
1999-12-08 13
6.3 General
Power supply
current outputs: 20...35 VDC 17...24 VAC
min. 12 +
R
L
(ohm)
50
0...1 V 9...35 VDC 9...24 VAC
0...5 V 15...35 VDC 12...24 VAC
0...10 V 20...35 VDC 16...24 VAC
Current consumption 6...10 mA + output currents
Electrical connections screw terminals for 0.5 - 1.5 mm
2
wires (AWG
15...20), stranded wires recommended
Alternative analogue
output signals (scalable) 0...20 mA (4...20 mA)
0...1 V, 0...5 V, 0...10 V
NOTE! Output scales correspond to 0…100 %RH and -40…+60°C.
External loads for
current outputs < 500 Ω
0...1 V > 1 kΩ (to ground)
0...5 V > 5 kΩ (to ground)
0...10 V >10 kΩ (to ground)
Operating temperature range
for electronics -20...+60 °C
with display option 0...+50 °C
Storage temperature range -40...+80 °C
Operating humidity range 0...100 %RH
Bushing for ∅ 7...10 mm cables
Sensor protection
standard membrane filter, part no. 17039HM
option plastic grid, part no. 17038
Cable length of HMP143A
standard 2.5 m
maximum 100 m (user extendable, see Appendix 3)
Housing material ABS plastic
Housing classification IP65 (NEMA 4)