Vaisala HUMICAP HMW90 SERIES Especificaciones Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 74
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
545
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
ROOM, DUCT, AND OSA 5% HUMIDITY TRANSMITTERS
KH5 SERIES
Accuracy 5% RH @ 73°F (23°C) from 5% to
90% RH; (0%-5% & 90%-100%)
add 5%
Drift <±0.5% drift per year
Thermal Effect 0.05%/°F
Supply Voltage 9.5- 28 VDC
Signal Output 4-20 mA = 0% to 100% RH, two-wire,
loop-powered Passive temperature
output: All Kele standard thermistors
and RTDs
Maximum Output Impedance
(Supply voltage - 9.5 VDC) / 0.02,
725Ω @ 24 VDC
Sensing Technology Precon HS-2000 capacitive
Operating Temperature -20° to 158°F (-29° to 70°C)
Enclosure Rating
KHR White plastic, UL94HB
KHD Metal handy box
KHO NEMA 3R plastic box
Probe
KHD 1/2" aluminum tube with expanded
Teflon® filter
KHO 1/2" aluminum tube with 40 micron
stainless steel sintered filter
Wiring Terminations Screw terminals
Weight (without options)
KHR 0.2 lb (0.09 kg)
KHD 1.2 lb (0.54 kg)
KHR 0.5 lb (0.23 kg)
Approvals RoHS
Warranty 18 months
DESCRIPTION
The Kele KHR, KHD, and KHO Series Humidity
Transmitters are specifically designed for use in HVAC/BAS
applications. These instruments measure relative humidity
from 0% to 100%. The standard two-wire, 4-20 mA output
provides low-cost humidity monitoring for building control.
The RH transmitters are available with thermistor or RTD
temperature sensors. They come in room (KHR), duct (KHD),
and OSA (KHO) mounting styles.
FEATURES
Calibration-free interchangeable sensors
Twelve-point computerized calibration
J1
12-28
VDC
4-20 mA
RH signal
Optional
temperature
sensor to
controller
V+
TTRH
THRM THRM
24 VDC
Power
supply
WIRING
SPECIFICATIONS
Vista de pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 73 74