549
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
ROOM, DUCT, AND OSA 5% HUMIDITY TRANSMITTERS
A/RH5 SERIES
Accuracy ±5% @ 77°F (25°C) from
10% to 95%
Thermal Effect <0.005% per °F (<0.01 per °C)
Supply Voltage 12-40 VDC or 24 VAC, selectable
Signal Output 4-20 mA, 0-5 VDC, 0-10 VDC
(field selectable)
Measurement Range 0% to 100%
Sensing Technology Capacitive
Operating Temperature
Room 32° to 122°F (0° to 50°C)
Duct/OSA -40° to 140°F (-40° to 60°C)
Dimensions
Room 3.8"H x 2.8"W x 0.9"D
(9.8 x 7 x 2.3 cm)
Duct 3.6" (9 cm) Ø head with 8.15"L
(20 cm) probe 0.75" (1.9 cm) Ø
OSA 3.6" (9 cm) Ø head with 3.0"L
(7.6 cm) probe 1.4" (3.6 cm) Ø
Enclosure
Room Plastic Delta-style
Duct/OSA Plastic weatherproof
Weight
Room 0.22 lb (0.1 kg)
Duct 1.2 lb (0.54 kg)
OSA 0.6 lb (0.27 kg)
SP 0.2 lb (0.09 kg)
Approvals CE, RoHS
Warranty 5 years
DESCRIPTION
The ACI A/RH5 Series Relative Humidity Transmitters
utilize a capacitive sensing element to deliver a proportional
4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output. It is available
for room, duct, outside, and stainless steel wall plate
applications. The A/RH5 Series has on board DIP switches
which allow the user to select the desired output signal and
can be powered by AC or DC power sources.
FEATURES
• Popular room housing
• Five-year warranty
• Duct and OSA twist-off NEMA 4 housing
• 24 VDC or 24 VAC power
• Field selectable current or voltage outputs
• Single point field calibration
• Digital display option
• Optional temperature sensor
SPECIFICATIONS
A/RH5-R
A/RH5-SP
A/RH5-O
A/RH5-D
Output Selection Switches (SW 1)
4-20 mA Output
0-10 VDC Output
0-5 VDC Output
ON ON
ON
ON
ON
ON
OFF
OFF
OFF
WIRING
2 Wire Current Output Signal
3 Wire Current Output Signal
Voltage Output Signal
DC Supply Voltage
4-20 mA Output
Supply Ground / Signal Common
AC or DC Supply Voltage
0-10 or 0-5 VDC Output Signal
4-20 mA Output
4-20mA VIN COM VOUT
AC or DC Supply Voltage
Supply Ground / Signal Common
4-20mA VIN COM VOUT
4-20mA VIN COM VOUT