Appendix C ______________________________________________________ MODBUS Reference
VAISALA ______________________________________________________________________ 199
Status Registers (Read-Only)
Table 39 Status Registers
Name Address Description
Fault status 0513 1 = No errors
Online status 0514 1 = Online data available
Error code (bits 15…0) 0516
Error code (bits 31…16) 0517
Bit field that represents the
error codes listed in Table 32
on page 152.
Active errors are
set to 1. For example, if bit 14
is set to 1, error co
de E14 i
s
active.
Error information can retrieved also with function code 08, sub-function
02.
NOTE
Basic status information of the HMT330 transmitter is also available with
the Read Exception Status function code 07. For details, see section
Exception Status Outputs on page 200.
Configuration Registers
Configuration parameter registers are used to configure the measurement.
Writing out-of-range values is silently ignored.
Table 40 Configuration Parameter Registers
Name Float Integer Valid Range
Pressure setting default
value
0769…0770 1025 (×1) 0…9999 hPa
Pressure setting
temporary value
0771…0772 1026 (×1) 0…9999 hPa
Chemical purge interval 0773…0774 1027 (×1) 10…2880 min
Molecular weight for
ppm
w
calculation
0775…0776 1028 (×0.001) 0…999.999
g/mol
If you modify the pressure setting repeatedly, modify the temporary
value at register 0771...0772 (1026) instead of the permanent setting at
register 0769…0770 (1025). Set the temporary value to zero to return to
the default pressure setting.
Non-metric units are not available on MODBUS. If they are needed,
calculate the conversion outside the transmitter.