www.vaisala.com
112 113
GMM112 Carbon Dioxide Module
for HVAC Applications
The Vaisala CARBOCAP
®
Carbon Dioxide Module GMM112 is a basic CO
2
measurement module.
Features/Benefits
▪
Compact, OEM module for
demand-controlled ventilation
and other CO
2
measurement
applications
▪
Incorporates Vaisala
CARBOCAP®, the silicon based
NDIR sensor with unique
internal referencing
▪
Advanced, single-beam, dual
wavelength measurement with
no moving parts
▪
Excellent long-term stability
▪
Ideal for ventilation control in
all types of occupied spaces
Most of us spend 90% of our time
indoors. Consequently, good indoor
air quality is important to our
wellbeing. All human beings produce
carbon dioxide gas by respiration,
thus the carbon dioxide level can
be used as an indicator for indoor
human presence. A high CO
2
level is a
sign of poor ventilation and often an
indication of other unpleasant odors
in the air. In many buildings the
ventilation need varies throughout
the day. Demand controlled
ventilation is an economical way to
ensure good air quality.
The Vaisala CARBOCAP
®
CO
2
sensors have been proven to be
accurate and durable. They have
an excellent long-term stability,
which decreases maintenance. The
superior performance of Vaisala
CARBOCAP
®
sensors results largely
from the stable reference provided by
the electrically tunable Fabry-Perot
Interferometer (FPI).
The tunable FPI lter measures CO
2
absorption, and simultaneously a
reference wavelength. This internal
reference measurement compensates
effectively for any changes in the
optical path, such as light source
intensity changes and contamination.
In the HVAC market, this type of
reference measurement is a unique
feature to Vaisala CARBOCAP
®
products, distinguishing them
from competitors’ comparative
products that do not have a reference
measurement at all, or have an
indirect reference measurement,
which is based on an assumed back-
ground CO
2
levels. In buildings with
around-the-clock occupancy (e.g.
hospitals, work-places, residential
buildings, retirement homes), the
assumed background CO
2
level
reference is simply not applicable.
The true internal reference
measurement of Vaisala CARBOCAP
®
CO
2
transmitters provides years of
stable CO
2
measurements.
The GMM112 Carbon Dioxide Module is
designed especially for DCV (Demand
Controlled Ventilation) applications
with three optional CO
2
measurement
ranges of 0…2000 ppm, 0…5000 ppm
and 0…10000 ppm.
mA
V
0
B
A
0
24V
mA
V
0
B
A
0
24V
25656
30
60
96
Ø3.2
Technical data
Performance
CO
2
-measurement range 0 ... 2000 ppm
0 ... 5000 ppm
0 ... 10000 ppm
Accuracy (including repeatability, non-
linearity and calibration uncertainty)
± (2 % of range + 2 % of
reading
Long-term stability ± 5 % of range/5 years
Response time T90 1 min
Temperature dependence, typical -0,35 % of reading / °C
Pressure dependence, typical +0,15 % of reading/hPa
Warm-up time 1 min, 10 min for full.
specification
Product lifetime > 10 years
Operating environment
Temperature -5 ... +45 °C (23 ... 113 °F)
Humidity 0 ... 85 %RH
Pressure 700 ... 1200 hPa
Electromagnectic compatibility
Complies with EMS standard EN61326-1:1997 + Am1:1998,
Generic Environment
Inputs and outputs
Operating voltage 24 V (±20 %) AC/DC
Power consumption <2 W
Outputs 4 … 20 mA, 0 … 10 V,
RS-485, 2-wire, non-isolated
Dimensions
Dimensions in mm
Ref. B210567EN-D ©Vaisala 2009
This material is subject to copyright protection, with all copyrights
retained by Vaisala and its individual partners. All rights reserved.
Any logos and/or product names are trademarks of Vaisala or
its individual partners. The reproduction, transfer, distribution or
storage of information contained in this brochure in any form
without the prior written consent of Vaisala is strictly prohibited.
All specifications — technical included — are subject to change
without notice.
For more information, visit
www.vaisala.com or contact
us at sales@vaisala.com