User's Guide _______________________________________________________________________
44 ___________________________________________________________________ M210934EN-D
Modbus Communication
The Modbus variant used in MMT162 communication is Modbus RTU.
Below is an example of a request to read the currently measured
temperature value from transmitter with address 240, and the response
from the transmitter.
Request to read registers 3 and 4 (currently measured value of T):
address
code
first register
registers to
Response as IEEE 754-2008 binary32 (41BBA77Ch = 23.4568 °C):
address
code
data bytes to
first register
second
For a list of available Modbus registers, see Appendix A Modbus
Reference on page 70.
Accessing Serial Port Command Interface from
Modbus Mode
You cannot change configuration settings (other than Modbus address)
while the device is in the Modbus mode. To use the configuration
commands on a Modbus-enabled device:
1. Connect the USB service cable to the PC and install the driver, if
necessary.
2. Open the terminal program and open a connection to the
corresponding COM port using settings 19200, 8, N, 1, no flow
control.
3. Plug the service cable to the connector II of the instrument.
4. In less than three seconds, send a hash character (#) and carriage
return (Enter) to the device using the terminal program. The device
is now ready for configuration commands. The Modbus mode is
restored on next power-up unless Modbus is disabled with
command SMODE.
For example, if you want to deactivate the Modbus mode on a MMT162
device, follow the procedure above and deactivate the Modbus mode
with command SMODE STOP. On subsequent power-ups, the serial
command interface will be activated.