User's Guide ______________________________________________________________________
com2_baud
1 = 1200
2 = 2400
3 = 4800
4 = 9600
5 = 19200
6 = 38400
7 = 57600
Baud rates for serial ports COM1 and
COM2. Changes take effect only after
reset or the RESET command.
Note that a low bit rate can affect
measurement timing, if WMT700 cannot
send the data message before a new
measurement starts.
com2_data
8 = 8 data bits
Data bits for serial ports COM1 and
COM2. Changes take effect only after
reset or the RESET command.
COM1 and COM2 Response delay in
milliseconds.
1 = RS-422
2 = SDI-12
Interface for serial port COM2. (The
interface for serial port COM1 cannot be
changed.)
com2_parity
1 = Even
Parity for serial ports COM1 and COM2.
Changes take effect only after reset or
Protocol for serial port COM1.
0 = WMT700
2 = WS425 F/G ASOS
3 = WS425 A/B ASCII
4 = WS425 A/B NMEA Standard
5 = WS425 A/B NMEA Extended
6 = WS425 A/B WAT11
8 = MES12
Protocol for serial port COM2.
0 = WMT700
1 = SDI-12
2 = WS425 F/G ASOS
3 = WS425 A/B ASCII
4 = WS425 A/B NMEA Standard
5 = WS425 A/B NMEA Extended
6 = WS425 A/B WAT11
8 = MES12
com2_stop
2 = 2 bits
Stop bits for serial ports COM1 and
COM2.
Changes take effect only after reset or
1 = Active pull-down
2 = Active pull-up
AOUT1 frequency output type. Setting 1
requires external pull-up resistor.
Setting 2 requires external pull-down
1 = Automatic
Heater control. When the value is set to
1, WMT700 controls the heaters based
on the temperature and other conditions.
1 = Enabled
Response for parameter setting.
206 __________________________________________________________________ M211095EN-E