16
Technical Data
°C
°C
0
0-80 -60 -40 -20 20 40 60 80 100 120 140 160
180
-0.7
-0.6
-0.5
-0.4
-0.3
-0.2
-0.1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Temperature sensor Pt100 RTD Class F0.1 IEC 60751
Other available variables (model-dependent)
dew point temperature, mixing ratio, absolute humidity, wet
bulb temperature, enthalpy, water vapor pressure
Performance
RELATIVE HUMIDITY
Measurement range 0 ... 100 %RH
Accuracy (including non-linearity, hysteresis, and repeatability)
with Vaisala HUMICAP
®
180 or 180R* for typical applications
with Vaisala HUMICAP
®
180C or 180RC* for applications with
chemical purge/warmed probe
at +15 ... +25 °C (59 ... +77 °F) ±1 %RH (0 ... 90 %)
±1.7 %RH (90 ... 100 %RH)
at -20 ... +40 °C (-4 ... +104 °F) ±(1.0 + 0.008 x reading) %RH
at -40 ... +180 °C (-40 ... +356 °F) ±(1.5 + 0.015 x reading) %RH
Factory calibration uncertainty (+20 °C) ±0.6 %RH (0 ... 40 %RH)
±1.0 %RH (40 ... 97 %RH)
(Defined as ±2 standard deviation limits. Small
variations possible; see also calibration certificate.)
Response time (90%) at +20 °C (+68 °F) 8 s/17 s** with grid filter
in still air 20 s/50 s** with grid + steel netting filter
40 s/60 s** with sintered filter
*HUMICAP 180R or 180RC recommended
**with HUMICAP 180R or 180RC sensor
TEMPERATURE
Accuracy at +20 °C (+68 °F) ± 0.2 °C (± 0.36 °F)
Accuracy over temperature range (measurement range
depends on model)
Ethernet interface (optional)
Supported standards 10BASE-T, 100BASE-TX
Connector 8P8C (RJ45)
IPv4 address assignment DHCP (automatic), static
Protocols Telnet, MODBUS TCP/IP
WLAN interface (optional)
Supported standards 802.11b
Antenna connector type RP-SMA
IPv4 address assignment DHCP (automatic), static
Protocols Telnet, MODBUS TCP/IP
Security WEP 64/128, WPA2/802.11i
Authentication / Encryption (WLAN)
Open / no encryption
Open / WEP
WPA Pre-shared key / TKIP
WPA Pre-shared key / CCMP (a.k.a. WPA2)
Optional data logger with real-time clock
Logged parameters max. four with trend/min/max values
Logging interval 10 sec. (fixed)
Max. logging period 4 years, 5 months
Logged points 13.7 million points per parameter
Battery lifetime min. 5 years
Display LCD with backlight, graphical trend display
of any parameter
Menu languages English, Chinese, Finnish, French, German,
Japanese, Russian, Spanish, Swedish
Inputs and Outputs
Operating voltage 10 ... 35 VDC, 24 VAC ±20%
with optional power supply module 100 ... 240 VAC, 50/60 HZ
Power consumption at +20 °C (U
in
24 VDC)
RS232 max. 25 mA
U
out
2 x 0 ... 1 V/0 ... 5 V/0 ... 10 V max. 25 mA
I
out
2 x 0 ... 20 mA max. 60 mA
display and backlight + 20 mA
during chemical purge max. 110 mA
during probe heating (HMT337) + 120 mA
Analog outputs (2 standard, 3rd optional)
current output 0 ... 20 mA, 4 ... 20 mA
voltage output 0... 1 V, 0... 5 V, 0... 10 V
Accuracy of analog outputs at +20 °C ±0.05% full scale
Temperature dependence of the
analog outputs ±0.005%/°C full scale
External loads
current outputs R
L
< 500 ohm
0 ... 1 V output R
L
> 2 kohm
0 ... 5 V and 0 ... 10 V outputs R
L
> 10 kohm
Max. wire size 0.5 mm
2
(AWG 20)
stranded wires recommended
Digital outputs RS232, RS485 (optional)
Protocols ASCII commands, MODBUS RTU
Service connection RS232, USB
Relay outputs (optional) 0.5 A, 250 VAC