LASTVAL Command
If the value in the report changes to ////, you can check the
measurement’s/sensor’s value with the LASTVAL command. Give the
command in the terminal connection. When you use the raw parameter,
the measured value before any validation and the status produced
during validation are shown. When you use the corresponding signal
name, the validated value is shown.
LASTVAL [Measurement] [raw | Signal name]
Examples:
The command with the signal name parameter (in the following case
TA) produces the following response:
/ > LASTVAL TAMeasQMH101_1 TA
Status:1 Value:20.490570
The measurement TAMeasQMH101_1 is defined in the setup file. The
command with the raw parameter produces the following response:
/ > LASTVAL TAMeasQMH101_1 raw
Status:1 Value:20.490570
where
Measurement = The name of the measurement as it is defined in
the MAWS setup file.
raw = The parameter that gives the status and the value
of the measurement before validation.
Signal name = The parameter that gives the validated value of
the measurement.
where
Status:1 = The value is valid.
Value:20.490570 = The validated value for the temperature
measurement is 20.49xxxx