Chapter 8 ____________________________________________________________ Technical Data
VAISALA______________________________________________________________________ 215
Channel B can be used either in the RS-485 mode or in the RS-232
mode. In 2-wire RS-485, both transmitted and received data is sent via
this channel. In 4-wire RS-485, this channel can either transmit or
receive depending on the configuration.
Figure 156 on page 214 provides a schematic wiring diagram for the
dual RS-485 connection, the dual 2-wire connection utilizing both
channels. The correct jumper settings for the channel B are listed in
Table 38 on page 215. The jumpers are located on the module as
illustrated in Figure 157 on page 215.
0201-049
Figure 157 DSI486 Default Jumper Locations
Table 38 The Jumper Settings for Channel B in the RS-485
Mode
Jumper Connected
Pins
Function
X3 1-2 Sets the RS-485 mode active for the channel
B.
3-4
X6 1-2
X5 1-2 The line terminating resistor is in use with RS-
485.